Guide

Caravan Park and Marina Wiring: Sections 708 and 709 (2026)

Sections 708 and 709 for electricians: no PEN on pitch circuits, TT electrodes, one 30 mA RCD per socket, 4 per enclosure, heights, cables, A4 709 change.

Published 21 September 2026 · Updated 13 November 2026 · Certio Software Ltd

Caravan pitches and marina berths are two of the places where BS 7671:2018+A4:2026 and the law both rule out a PME earth for the outlet you provide. Regulation 9(4) of the Electricity Safety, Quality and Continuity Regulations 2002 bars connecting a combined neutral and earth to the metalwork of a caravan or boat, so pitch and berth circuits run on TT with their own electrodes. On top of that, every socket-outlet gets its own 30 mA all-pole RCD and its own overcurrent device, no more than four sockets share an enclosure, and the outlets are BS EN 60309-2. Amendment 4 also added a new marina regulation, 709.313.1.101, on isolating transformers. This guide covers the rules, the testing and how to code what you find.

Key takeaways
  • Section 708 covers caravan parks, camping parks and similar locations, including the circuits feeding residential park homes since the 2018 edition. Section 709 covers marinas and similar locations. Both stop at the outlet or connection point; the caravan itself is Section 721.
  • No PEN conductor in the final circuit to a caravan, tent, boat or park home (708.312.2.1), and no PME earth connected to caravan or boat metalwork (ESQCR 9(4), 708.411.4 and 709.411.4). TT for pitch and berth circuits is the norm.
  • One 30 mA all-pole RCD and one overcurrent device per socket-outlet (708.415.1, 708.533 and the 709 equivalents). A shared RCD across a pillar does not comply.
  • Sockets: at least 16 A, BS EN 60309-2, IP44 minimum, IK08, no more than four per enclosure. Pitch sockets 0.5 m to 1.5 m above ground; berth sockets at least 1 m above the highest water level (300 mm on a floating pontoon with splash protection).
  • Underground cables: 0.6 m minimum on a caravan park, 0.5 m typical at a marina. Overhead conductors insulated and at least 6 m up where vehicles move, 3.5 m elsewhere.
  • Amendment 4 added 709.313.1.101: hull-to-shore isolation equipment to BS EN 61558-2-4, with the supply PE not connected to the socket earth terminal.
  • IET GN3 suggests a one-year maximum interval for caravan parks and marinas.

What do Sections 708 and 709 actually cover?

Section 708 applies to the parts of a caravan park, camping park or similar site that supply leisure accommodation vehicles and tents: the distribution, the pitch supply equipment and the socket-outlets. Since BS 7671:2018 it also covers the circuits supplying residential park homes, which need individual overcurrent protection and a 30 mA RCD the occupier can reach. It does not cover the inside of the caravan. That is Section 721 (caravans and motor caravans), which sets the 25 m (±2 m) one-piece connecting lead with no joints, the BS EN 60309-1 inlet no higher than 1.8 m, and the onboard all-pole RCD.

Section 709 applies to marinas and similar locations: the fixed installation supplying pleasure craft and houseboats at a berth, including jetties, wharves, piers and pontoons. The vessel's own wiring is outside BS 7671.

Site buildings such as the shop, reception, laundry and shower block are not special locations under 708 or 709 just because they sit on the park. They are ordinary installations, and the shower block brings in Section 701.

Why is PME ruled out for pitches and berths?

On a PME supply the neutral and protective functions share one conductor in the network. If that PEN conductor breaks, every exposed-conductive-part connected to the PME terminal can rise towards line voltage. In a house, main bonding keeps everything inside the building at roughly the same potential. A caravan chassis, a set of metal steps or a hull is the opposite: a metal body connected by a lead to your supply, touched by someone standing on wet grass or a wet deck. Nothing holds the ground they stand on at the same potential.

The law deals with it first. ESQCR Regulation 9(4) prohibits connecting the neutral or a combined neutral and protective conductor to the metalwork of a caravan or boat. BS 7671 follows: 708.411.4 and 709.411.4 require that where the supply is PME, the pitch or berth circuits are separated onto a TT arrangement with an installation earth electrode. The separation can be made at the site distribution board or at the pitch supply points. The site buildings can stay on the PME terminal.

That separation is where faults hide. Look for armoured cable whose armour is terminated at the PME end and also glanded into a TT pillar, steel conduit or trunking bridging the two systems, and an old earth link left in place at the board. Any of those exports PME to the pitches by the back door.

How good does the TT electrode need to be?

On a TT system the RCD does the disconnecting, and Regulation 411.5.3 sets the condition RA × IΔn ≤ 50 V, where RA is the electrode resistance plus the protective conductor to the exposed parts.

RCD IΔn Maximum RA by 411.5.3 Touch voltage at IΔn with RA = 200 Ω
30 mA 1,667 Ω 6 V
100 mA 500 Ω 20 V
300 mA (time-delayed feeder) 167 Ω 60 V, fails

The 1,667 Ω limit is a design ceiling, not a target. GN3 notes that electrode readings above about 200 Ω may not be stable, and a rod that reads well in a wet November can be very different after a dry August. The last row matters on parks: a 300 mA time-delayed RCD on a TT pillar feeder needs an electrode under 167 Ω to meet 411.5.3 on its own, so check what is actually protecting the sub-main cable and the pillar enclosure, not just the sockets. The electrode guide at [Earth Electrode Testing for TT Systems: Methods and Limits](/guides/earth-electrode-testing-tt-systems) covers the measurement, and [Earthing Arrangements: TN-S, TN-C-S (PME, PNB) and TT](/guides/earthing-arrangements-tn-s-tn-c-s-tt-explained) the wider TT versus PME picture.

What are the socket-outlet rules on a pitch and at a berth?

Most park and marina observations come from the outlets, so here is the side-by-side.

Requirement Caravan pitch (Section 708) Marina berth (Section 709)
Socket standard BS EN 60309-2, or BS EN 60309-4 interlocked BS EN 60309-2 up to 63 A; BS EN 60309-1 above 63 A
Minimum rating 16 A 16 A single-phase generally
How many At least one per pitch One per craft or houseboat
Per enclosure No more than four No more than four
IP rating IP44 minimum IP44 minimum; IPX5 for water jets, IPX6 for waves
Impact IK08 or protected by location IK08 or protected by location
Height 0.5 m to 1.5 m above ground At least 1 m above highest water level; 300 mm on floating pontoons with splash protection
RCD Own 30 mA RCD per socket, all-pole Own 30 mA RCD per socket, all-pole
Overcurrent Own device per socket Own device per socket
Isolation At least one means in each distribution enclosure One isolator per four sockets max, and one per cabinet, line and neutral

"Individually protected" is the phrase people miss. A pillar of four blue sockets behind one 30 mA RCD does not comply. In practice the clean answer is a 30 mA all-pole RCBO per outlet. Both sections also say the socket should be as close as practicable to the pitch or berth. The Section 721 lead is 25 m (±2 m) in one piece, so a pillar that forces people to join leads, or to run a lead across a roadway, is a design problem.

The lead is not trivial either. As an illustration, a 16 A load on 25 m of 2.5 mm² two-core flex at 18 mV/A/m drops about 7.2 V (3.1% of 230 V) before the caravan's own wiring. Add the pillar sub-main and a site at the end of a long rural supply and pitch voltages sag quickly, so size sub-mains with that in mind.

What does Section 709 add for marinas?

Water, movement and corrosion. Equipment on or above a jetty, wharf, pier or pontoon has to cope with splashing, jets or waves (IPX4, IPX5 or IPX6), salt-laden air and impact.

Wiring is restricted. For distribution, buried cables, insulated overhead cables, and armoured thermoplastic or elastomeric cables with non-hygroscopic fillers are listed. On or above a jetty, wharf, pier or pontoon, the summary of 709.521 published by Professional Electrician says not to use cables suspended in free air or on a catenary, non-sheathed cables in containment, aluminium-conductor cables or mineral insulated cables. Floating sections flex with the tide, so allow slack or use flexible cable at hinges and ramps, and give conduit and trunking a fall or drain points. IET Wiring Matters (Summer 2007) adds that galvanised steel armour should not be relied on as the circuit protective conductor on floating sections, though it is still connected to earth.

The Amendment 4 change sits here. The SELECT "2026 Amendment 4: What's New" summary says new Regulation 709.313.1.101 requires that, between the hull of the vessel and metallic parts on the shore side, equipment to BS EN 61558-2-4 is used, and that the protective conductor of the supply to the isolating transformer is not connected to the earth terminal of the socket-outlet supplying the vessel. The aim is to stop galvanic currents corroding hulls and pontoon steelwork. If a marina has transformer pedestals, check the transformer standard and that the PE arrangement matches. Read the regulation itself before designing to it.

The operator should also post an instruction notice at each socket or group of sockets telling boat owners how to connect and disconnect safely (Section 709 gives a model notice).

How should cables be run across a park?

Section 708 treats the ground as hostile: tent pegs, ground anchors, awning stakes and the groundsman's post-hole borer. Underground cables should generally be at least 0.6 m deep, or given additional mechanical protection, and routed outside areas where pegs are likely to go in. Record the routes on a site drawing. A park with no cable plan is a limitation worth writing down.

Overhead conductors must be insulated. Clearance is at least 6 m where vehicles move and 3.5 m elsewhere, and poles need protecting from vehicles. A touring caravan's roof aerial or a motorhome reversing onto a pitch is exactly what that 6 m is for.

Distribution enclosures need a means of isolation inside each one, and the RCD test buttons should be usable by the warden without exposing live parts.

How do you inspect and test a park or marina?

Treat it as a commercial EICR with a special-location overlay, and agree the extent in writing. A 150-pitch park can have 40 pillars and kilometres of cable, so you will sample. Record the sampling and the limitations on the report, as set out in [EICR Sampling and Limitations Explained: Extent, LIM and N/V](/guides/eicr-sampling-and-limitations-explained).

  1. Origin. Record the supply earthing for the site buildings, and separately how the pitch or berth distribution is earthed. Measure Ze at the intake and Zdb at each pillar board.
  2. Electrode. Measure each TT electrode with an earth electrode tester where you can, not only an earth loop reading. Note the weather and ground conditions.
  3. Separation test. Disconnect the pitch earth at the board and prove there is no continuity back to the PME terminal through armour, conduit or a forgotten link. On parks this one check finds more trouble than any other.
  4. Pillar feeders. Insulation resistance at 500 V with a minimum of 1 MΩ, continuity of protective conductors, polarity.
  5. Every sampled outlet. Polarity, Zs, and an RCD test at IΔn (300 ms for a general-type device; the 5 × IΔn test has not been required since A2:2022). Check that each socket really has its own RCD by tripping one and confirming its neighbours stay on.
  6. Visual. Missing or cut glands, water inside pillars, broken socket flaps, corroded electrode clamps, overhead line clearances, shallow cable at pitch edges. At a marina add hinge and ramp cables, outlet height against the high-water mark, and modified shore leads.

The detail on insulation resistance is in [Insulation Resistance Testing: Voltages, Minimums and Method](/guides/insulation-resistance-testing-guide), and on RCD testing in [RCD Testing Explained: The One Test BS 7671 Now Requires](/guides/rcd-testing-explained). Three-phase pillars for large units follow [Three-Phase Testing: Rotation, IR, Zs, PFC and RCDs](/guides/three-phase-testing-basics).

How should you code what you find?

BS 7671 sets the requirement; the code is your judgement of risk. On the A4 model forms only C1 and C2 make the report unsatisfactory, and FI is advisory. These are reasonable starting points, not a published list.

Finding Typical code Why
Pitch or berth circuit earthed to the PME terminal C2 Lost-PEN fault would put the caravan or hull at a dangerous potential; contrary to ESQCR 9(4)
Socket with no 30 mA RCD at all C2 Outdoor mobile equipment without additional protection
Working 30 mA RCD shared by several sockets C3 Protection exists but not individual as 708.415.1 requires
TT electrode reading fails RA × IΔn ≤ 50 V C2 Fault protection not achieved
Electrode not accessible or not measured Limitation, or FI if there is evidence of a problem Record why
BS 1363 socket used as a pitch or berth supply C3 or C2 depending on RCD and condition Wrong outlet type for the location
Cable shallow under a pitch, exposed to pegs C2 Real risk of penetration
Overhead line below 6 m over a roadway C2 Vehicle contact risk
Water inside a pillar, live parts accessible C1 Immediate danger
More than four sockets in an enclosure C3 Non-compliance with limited direct risk

The same TT versus PME decision on a smaller scale is in [Outbuilding Supply: SWA, PME or TT Earth, Volt Drop and Tests](/guides/outbuilding-garden-supply-swa-tt-pme), and the pool or hot tub at the leisure park is Section 702, covered in [Hot Tub and Pool Wiring: Section 702 Zones, RCDs and PME](/guides/hot-tub-swimming-pool-section-702).

How Certio helps

Certio produces the EICR, EIC, Minor Works certificate and PAT records on the BS 7671 model forms and turns them into branded PDFs. Photograph the consumer unit and the circuit schedule drafts itself; point the phone camera at a Megger MFT-X1 and the reading goes straight into the schedule of test results, or dictate it while your hands stay on the probes. Suggested observation wording with the regulation reference is there for you to check and confirm. The judgement stays yours; the typing goes. Starter is £4.99 a month, charged when you sign up.

Straight answers

Questions

Can a caravan pitch supply be earthed to a PME terminal?
No. Regulation 9(4) of the ESQCR 2002 bars connecting a combined neutral and earth to the metalwork of a caravan or boat, and Regulation 708.411.4 reflects that. Where the site is fed from PME, the pitch circuits are separated onto a TT arrangement with their own earth electrodes, at the distribution board or at the pitch supply points, and the electrode must satisfy RA × IΔn ≤ 50 V.
How many socket-outlets can go in one caravan pitch pillar?
No more than four socket-outlets may be grouped in one enclosure, with at least one socket-outlet for each pitch. Each socket must be BS EN 60309-2 (or a BS EN 60309-4 interlocked unit), rated at least 16 A, at least IP44 and IK08, mounted 0.5 m to 1.5 m above ground, with its own 30 mA RCD and its own overcurrent device.
Can one 30 mA RCD protect all the sockets on a pillar?
No. Sections 708 and 709 both require each socket-outlet to be individually protected by an RCD of not more than 30 mA that disconnects all live conductors including neutral, plus its own overcurrent device. In practice that means an all-pole 30 mA RCBO per outlet. A shared RCD across several pitches does not comply, and a fault in one caravan trips the neighbours.
What did Amendment 4 change for marinas?
Amendment 4 to BS 7671 added Regulation 709.313.1.101. Where isolation is provided between the hull of a vessel and the shore-side metalwork to stop galvanic corrosion, the equipment must conform to BS EN 61558-2-4, and the protective conductor of the supply to the isolating transformer must not be connected to the earth terminal of the socket-outlet supplying the vessel.
How often should a caravan park or marina be inspected?
IET Guidance Note 3 recommends a maximum interval of one year for caravan parks and for marinas, because the equipment is outdoors, handled by the public and exposed to weather and water. Touring caravans themselves fall under Section 721 and are usually given three years. Site licence conditions and insurers often ask for the annual report as evidence.
Less typing, same judgement

Down tools at 5. The paperwork's already done.

Certio lays out EICR, EIC, Minor Works and PAT certificates to the BS 7671 model forms and produces branded PDFs. Photograph the board and the schedule drafts itself; point the camera at a Megger MFT-X1 and the reading goes straight in. There's a free plan with no card. Starter is £4.99 a month and Pro £9.99 with unlimited certificates, charged when you sign up.

Get Starter · £4.99/mo →

More on EICR software and AI EICR software.