Section 702 of BS 7671:2018+A4:2026 covers the basins of swimming pools, fountains and paddling pools. It does not name hot tubs, but IET Guidance Note 7 recommends applying it in full to an outdoor tub. The zones are fixed: zone 0 is the water, zone 1 runs 2 m out from the rim and 2.5 m up, and zone 2 runs a further 1.5 m. In zones 0 and 1 only SELV at no more than 12 V a.c. or 30 V ripple-free d.c. is allowed, with the source outside all the zones. Put the isolator at least 2 m from the tub, on a 30 mA RCD.
- Section 702 does not name hot tubs. GN7 says apply it in full outdoors; indoors, a tub in a bathroom falls under Section 701.
- Zones: 0 is the basin, 1 is 2 m from the rim and 2.5 m high, 2 is a further 1.5 m. Fountains have no zone 2.
- No switchgear, sockets or accessories in zone 0 or 1. In zone 2 they need SELV, electrical separation or a 30 mA RCD.
- IP ratings: IPX8 in zone 0, IPX4 in zone 1, IPX2 indoors or IPX4 outdoors in zone 2, and IPX5 wherever jet washing is likely.
- BS 7671 allows PME, but ENA G12/4 recommends TT for pools. Section 702 notes an electrode of about 20 Ω or less where PME is used.
- A dedicated hot tub supply is a new circuit, so it needs an EIC and, in England, Part P notification.
Does Section 702 actually apply to a hot tub?
Regulation 702.11 sets the scope as the basins of swimming pools, fountains and paddling pools. Hot tubs, spas and plunge pools aren't in it. That gap is where the arguments on forums come from, and the main guidance bodies don't say quite the same thing.
The July 2021 Wiring Matters article on hot tubs (issue 86) points out that the reason Section 702 exists is lower body resistance in water, and that applies just as much to a tub on a patio. It quotes IET Guidance Note 7, Chapter 13.8: outdoors, "it is recommended that the requirements of Section 702 should be applied in full". For a tub inside a room with a bath or shower, Section 701 applies instead. NAPIT's January 2021 article in Professional Electrician takes a narrower view. It says Section 702 applies to commercial tubs and tubs built into the ground, and that in other cases it can be used as the design basis where there's doubt.
In practice both lead to the same design for a domestic outdoor tub: zones taken from Section 702, an isolator outside zone 1, and 30 mA RCD protection. The tub itself is built to BS EN 60335-2-60, where it is called a "whirlpool spa". That product standard sends the installer back to the national wiring rules, and Regulation 510.3 requires you to take account of the manufacturer's instructions.
Where are zones 0, 1 and 2?
Measure the zones from the edge of the basin, not from the pump house or the plant room. As in a bathroom, a fixed wall or partition limits a zone. If a solid barrier stops you reaching a point from the water, that point is outside the zone.
| Zone | Horizontal extent | Height | Typical contents |
|---|---|---|---|
| 0 | Inside the basin, including openings in its walls or floor accessible to people in it | Water | Underwater luminaires, jets — SELV 12 V a.c. / 30 V d.c. only |
| 1 | 2 m from the edge of the basin | 2.5 m above the floor or standing surface | Steps, rails, diving boards, tub surround |
| 2 | 1.5 m beyond zone 1 (3.5 m from the rim) | 2.5 m above the floor | Isolators, sockets, lighting, heater plant |
Where there's a diving board, starting block or slide, zone 1 extends to 1.5 m around it and to 2.5 m above the highest surface a person can stand on. A tub sunk into decking still has its zones measured from the rim, so on most patios the back wall of the house falls in zone 1 or zone 2. These distances are much bigger than in a bathroom (0.6 m and 2.25 m under Section 701 — see the bathroom zones guide), so plan the isolator and outside-light positions before the slab goes down.
What protection is allowed in each zone?
In zones 0 and 1, Regulation 702.410.3.4.1 allows only SELV at a nominal voltage not above 12 V a.c. or 30 V ripple-free d.c., with the safety source outside zones 0, 1 and 2. A 70 V d.c. constant-current LED driver feeding step lights within 2 m of a tub is the classic problem. An IET EngX thread on hot tub lighting found exactly that installation, and the fix was a 24 V constant-voltage fitting confirmed as SELV by the manufacturer.
Regulation 702.55.4 makes an exception for pool equipment such as filter and jet pumps in zone 1. The equipment needs a Class II (or equivalent) enclosure with mechanical protection, opened only with a key or tool, and protection by SELV, electrical separation or a 30 mA RCD. Wiring Matters also describes the 702.55.4 lighting option where there is no zone 2: a Class II luminaire at least 2 m above the lower limit of zone 1, on an RCD-protected circuit. Metal Class I fittings within 2 m of the basin are out.
In zone 2 you choose one of three things: SELV, electrical separation feeding one item of equipment, or automatic disconnection with a 30 mA RCD. The RCD is the usual answer.
| Item | Zone 0 | Zone 1 | Zone 2 |
|---|---|---|---|
| Socket-outlet | No | No (see small-pool exception below) | Yes, with SELV, separation or 30 mA RCD |
| Switch or isolator | No | No | Yes, with SELV, separation or 30 mA RCD |
| Junction box | No | SELV only | Yes |
| Luminaire | SELV 12 V a.c. / 30 V d.c. | SELV, or 702.55.4 conditions | 30 mA RCD, IPX4 outdoors |
| Pump or filter unit | Made for zone 0 | 702.55.4 enclosure + protection | 30 mA RCD |
For a small pool where switchgear can't be kept out of zone 1, Regulation 702.53 allows a socket-outlet or switch there only if it's at least 1.25 m from the zone 0 boundary and at least 0.3 m above the floor, and protected by SELV, electrical separation or a 30 mA RCD. That's meant for a tight plant room, not as permission to put a socket next to a hot tub.
Where does the hot tub isolator go?
Fit it at least 2 m from the edge of the tub. Wiring Matters calls this best practice, and NAPIT's guidance gives the same 2 m. That puts it outside zone 1 and inside zone 2, so it must be on the RCD-protected circuit and rated at least IPX4 outdoors. Rotary isolators and weatherproof sockets are normally IP65. It also has to work as an effective means of isolation under Regulation 132.15.201. In practice that means it is within sight of the tub and someone can reach it without getting in the water.
Plug-and-play inflatable tubs come with a 13 A plug and usually a PRCD in the lead. A single weatherproof socket in zone 2 on a 30 mA RCD suits them. Hard-shell tubs typically need a 32 A or 40 A hard-wired supply. If the supplier makes the final connection, NAPIT suggests leaving a tail of H07RN-F (BS EN 50525-2-21), allowing about 5 m if you have no figure. Terminate it in a temporary weatherproof junction box rather than leaving it locked off and bare, and note on the EIC that the final connection was made by others.
What IP ratings apply?
Regulation 702.512.2 sets these minimums:
| Zone | Minimum IP | Where water jets are used for cleaning |
|---|---|---|
| 0 | IPX8 | IPX8 |
| 1 | IPX4 | IPX5 |
| 2 indoors | IPX2 | IPX5 |
| 2 outdoors | IPX4 | IPX5 |
Regulation 702.522.21 also prefers non-metallic containment within the zones. Steel trunking on a pool hall wall is the sort of thing an inspector will write up.
What supplementary bonding is required?
Regulation 702.415.2 requires local supplementary bonding to connect every extraneous-conductive-part in zones 0, 1 and 2 to the protective conductors of the exposed-conductive-parts there. That catches ladders, handrails, starting blocks, drain grates, metal floor grids and the reinforcement in a concrete pool shell. Size the conductors to Regulation 544.2: at least 2.5 mm² if mechanically protected and 4 mm² if not.
A moulded acrylic tub on a timber deck often has no extraneous-conductive-parts in its zones. If so, record that no supplementary bonding was needed and why. If a metal handrail is set in a concrete plinth, test it to earth. If it reads below about 22 kΩ, it's extraneous and needs bonding (the main bonding guide covers the test).
PME or TT for a hot tub?
Section 702 doesn't prohibit PME the way Regulation 722.411.4.1 restricts it for EV chargepoints. Many domestic tubs do run on a PME earth taken through SWA from the house board. The question is whether you can justify it.
Wiring Matters (July 2021) gives the numbers. With the supply at 253 V and a heavily loaded PEN dropping 36.8 V, the touch voltage on bonded metalwork can reach about 18.4 V in normal service. IEC TR 60479-5 puts the let-go threshold for a palm-sized contact at about 11 V a.c., and lower again for someone sitting in water. If the PEN breaks, everything connected to the MET, including the water through the heater element, can rise towards 230 V, and an RCD won't operate because no current is leaking from the circuit.
| Option | Pros | Cons | What to test |
|---|---|---|---|
| PME (TN-C-S) | Low Zs, no electrode | Open-PEN risk to someone in the water; ENA G12/4 6.5.2 recommends TT for pools, PME only with a bonded grid under the poolside | Zs against Table 41.3, bonding continuity |
| PME + local electrode | Section 702 note: connect an earth mat or electrode of about 20 Ω or less to the supplementary bonding | Still PME; electrode needs testing | RA of electrode, bonding |
| TT for the outdoor supply | Removes the PEN hazard at the tub | Needs separation from PME metalwork (Regulation 411.3.1.1) and an RCD for fault protection | RA, RA × IΔn ≤ 50 V (≤1,667 Ω at 30 mA), RCD trip time |
If you make the tub supply TT, keep its exposed metalwork out of reach of anything on the house's PME earth. That includes the shed, the outside tap pipework and the SWA armour. The earth electrode guide (TT testing) explains why GN3 treats an electrode above 200 Ω as possibly unstable, even though Table 41.5 allows far more. The outbuilding SWA guide covers the PME-versus-TT choice on SWA runs in more detail.
Worked example: 32 A hot tub on 25 m of SWA
Take a hard-shell tub on a 32 A Type B RCBO (Type A RCD element), fed by 25 m of 3-core 6 mm² SWA using the third core as the cpc, on a PME supply with Ze of 0.35 Ω.
| Check | Working | Result |
|---|---|---|
| R1+R2 at 20 °C | 25 m × (3.08 + 3.08) mΩ/m | 0.154 Ω |
| At operating temperature | 0.154 × 1.20 | 0.185 Ω |
| Expected Zs | 0.35 + 0.185 | 0.54 Ω |
| Table 41.3 max, B32 | 1.37 Ω (80% rule of thumb 1.10 Ω) | Pass |
| Volt drop | 32 A × 25 m × 7.3 mV/A/m ÷ 1,000 | 5.8 V (2.5%) — within 5% |
Take current ratings from the Appendix 4 table for armoured cables (4D4A) for the installation method you're using. Buried SWA has to meet Regulation 522.8.10: deep enough to avoid disturbance, with earthed armour, and marked with tape or tiles. If the design goes TT, the Zs line drops out and the RCD provides the fault protection, so test RA and the trip time instead.
What RCD type does a hot tub need?
The 30 mA rating is fixed. The type depends on the load. Regulation 531.3.3 requires the RCD type to suit the residual current the equipment can produce. Circulation pump speed controls and heater electronics can leak smooth d.c. that saturates a Type AC device. Wiring Matters suggests Type A where d.c. leakage is possible and says to check that upstream RCDs can cope too. Read the installation manual before ordering the RCBO. If the manufacturer asks for a particular type, Regulation 510.3 means you fit it. The RCD testing guide covers the test at IΔn.
Which certificate, and is it notifiable?
A dedicated hot tub supply is a new circuit, so it needs an Electrical Installation Certificate, not a Minor Works. In England, Approved Document P (2013 edition, GOV.UK) makes three kinds of work notifiable: a new circuit, a consumer unit replacement, or an addition or alteration in a special location. It defines a special location as the zone around a bath or shower, or "a room containing a swimming pool or sauna heater". So an outdoor tub circuit is notifiable because it is a new circuit. Adding a socket in an indoor pool hall is notifiable because of the location. Wales has a longer list of notifiable work, and Scotland uses building warrants. The Part P guide covers both.
On the EIC, record the earthing arrangement of the tub supply (say if it differs from the house), the RCD type and trip time, Zs at the isolator, insulation resistance of the SWA, whether supplementary bonding is present or not needed and why, and any final connection made by others.
What to look for on an EICR
Tubs are cheap now, so you'll find them on periodic inspections. These codes follow the reasoning in Electrical Safety First Best Practice Guide 4 and the observation coding guide:
| Finding | Typical code |
|---|---|
| Plug-in tub on an outdoor socket with no 30 mA RCD | C2 |
| Isolator or socket in zone 1, reachable from the water | C2 |
| Non-SELV lighting above 12 V a.c. / 30 V d.c. in zone 0 or 1 | C2 |
| Extraneous metal handrail in zone 1 not bonded | C2 |
| Type AC RCD where the manufacturer specifies Type A, RCD trips on test | C3 |
| Equipment below the required IP rating in zone 2 outdoors | C2 |
| Pump pack not opened, final connection not seen | Limitation, not a code |
FI is advisory on the A4 model form, but in England a written FI on a rented property still starts the landlord's 28-day investigation clock. Record the tub and the zone layout in the extent of the inspection.
How Certio helps
Certio produces the EICR, EIC, Minor Works certificate and PAT records on the BS 7671 model forms and turns them into branded PDFs. Photograph the consumer unit and the circuit schedule drafts itself; point the phone camera at a Megger MFT-X1 and the reading goes straight into the schedule of test results, or dictate it while your hands stay on the probes. Suggested observation wording with the regulation reference is there for you to check and confirm. The judgement stays yours; the typing goes. Starter is £4.99 a month, charged when you sign up.