Each safety observation on an Electrical Installation Condition Report (EICR) gets one classification code. The code tells the person who ordered the report how urgently something needs doing. The codes come from the model EICR in BS 7671. The industry reference for applying them is Electrical Safety First's Best Practice Guide 4 (BPG4), produced with input from bodies including the IET, NICEIC and NAPIT. Issue 7.4, dated August 2026, takes account of BS 7671:2018+A4:2026.

The four codes

C1

Danger present

People using the installation are at risk now, so remedial action is needed immediately. Where it's practicable, make it safe on discovery with the client's agreement, and tell them straight away in writing.

C2

Potentially dangerous

It isn't dangerous at the moment of inspection, but a fault or some other foreseeable event would turn it into an immediate danger. Remedial action is urgent.

C3

Improvement recommended

Not a source of immediate or potential danger, but putting it right would make the installation safer. It is advisory.

FI

Further investigation

You found a possible safety issue you couldn't classify within the agreed extent and limitations. The A4:2026 form says further investigation is advised.

Give each observation one code only. If more than one could apply, BPG4 says use the most serious.

How the codes decide the overall result

Under A4:2026 the rule is simple. Any C1 or C2 observation makes the overall assessment unsatisfactory. C3 and FI observations are advisory and don't change it. The A4 model form now splits the observations section in two: one list for C1 and C2 items, which drive the outcome, and a separate list for C3 and FI items, which don't. BPG4 adds that with no C1 or C2 observations it wouldn't be reasonable to call an installation unsatisfactory.

That is a change for FI. The notes on the A2:2022 model form told inspectors to mark an FI observation as unsatisfactory, and the code read as further investigation required without delay. The IET says A4 separated FI and C3 from C1 and C2 to make it clear they don't lead to an unsatisfactory outcome.

Check which version a report follows. A4:2026 was published on 15 April 2026. BS 7671:2018+A2:2022+A3:2024 stays current until it is withdrawn on 15 October 2026, so until then a report can follow either. The report records the amendment it was carried out to.

Typical examples of each code

These are paraphrased from the tables in BPG4 Issue 7.4. They aren't exhaustive, and the person signing the report is responsible for its content. BPG4 expects you to be able to justify any departure from it.

CodeExamples
C1Live parts that can be touched: a missing circuit-breaker with no blank fitted, a badly damaged accessory, or conductors with missing or damaged insulation. Metalwork made live by a fault. Incorrect polarity at the origin.
C2No reliable means of earthing, or a gas, oil or water pipe used as the earth. No effective main bonding to metal pipes or other extraneous-conductive-parts entering the building. A socket-outlet with no earth. No RCD for sockets likely to supply equipment used outdoors, or for a socket circuit in a room with a bath or shower. Zs too high for the device to disconnect in the time required when it was installed, with no RCD on the circuit. A borrowed neutral, a broken ring or a ring cross-connected with another circuit. Insulation resistance below 1 MΩ to earth. Connections showing signs of overheating.
C3No RCD for a socket that is unlikely to supply outdoor equipment and doesn't serve a bathroom. No RCD on lighting circuits in a home. Cables less than 50 mm deep in a wall with no RCD and no other protection. A Type AC RCD where a Type A is needed. A plastic consumer unit, not in a non-combustible enclosure, under a wooden staircase or on the only escape route. No AFDD in an HMO, a high-rise residential building, purpose-built student accommodation or a care home.

Findings that don't take a code

Issue 7.4 names three kinds of finding that shouldn't be coded:

  • Observations worth mentioning that aren't non-compliances, such as a consumer unit fitted high up, or no AFDDs in an ordinary house.
  • Non-compliances only: departures from BS 7671 that don't give rise to danger and needn't be recorded, such as old cable colours, or a plastic consumer unit that isn't under stairs or on an escape route.
  • Myths: things that aren't non-compliances at all, such as rewireable fuses that still protect the circuit properly, circuit-breakers to BS 3871, or sockets without switches.

Using FI properly

Periodic inspection isn't fault-finding. BPG4 says that in a domestic installation you should generally be able to code every observation without further investigation. FI is for a potential safety issue that the agreed extent or limitations stopped you getting to the bottom of.

The IET gives two examples of FI used wrongly. An unidentified circuit breaches Regulation 514.8.1, so code it: tracing the circuit is remedial work. An insulation resistance reading below 1 MΩ fails Table 64, so code it: finding the cause is fault-finding.

Writing observations that hold up

  • Describe what you found, not the repair. Price the remedial work on a separate quote.
  • Write for the person who ordered the report, in plain language, with the schedule reference. Photographs can be attached.
  • Record faults on the distributor's or supplier's intake equipment, but don't let them decide the outcome unless live parts are accessible. Advise the client to report dangerous intake equipment urgently; BPG4 points to the 105 number.
  • Make the recommended date for the next inspection conditional on C1 items being fixed immediately and C2 items urgently.
  • An installation built to an earlier edition isn't unsafe simply because it doesn't meet the current one.

Codes on rented homes

In England, the government's guidance for landlords says C1 and C2 observations need remedial work, C3s don't have to be acted on, and FI items must be investigated. That guidance dates from November 2025, before A4:2026 made FI advisory, so describe any FI precisely. Our guide to landlord EICRs in England covers the deadlines.

Straight answers

Questions

Does an FI code make an EICR unsatisfactory?
Not under BS 7671:2018+A4:2026. Only C1 and C2 observations make the overall assessment unsatisfactory, and C3 and FI are advisory. The A2:2022 model form, which can be used until 15 October 2026, told inspectors to mark an FI as unsatisfactory.
Can I give one observation two codes?
No. Each observation takes one code. If more than one could apply, Best Practice Guide 4 says to use the most serious, C1 being the most serious.
Is a plastic consumer unit a C3?
Only in certain places. Best Practice Guide 4 gives a C3 where a consumer unit made of combustible material, not inside a non-combustible enclosure, is under a wooden staircase or on the only escape route. Elsewhere it is a non-compliance that doesn't need a code.
Do I have to make a C1 safe before I leave?
Wherever it's practicable, and with the agreement of the owner or user, make it safe on discovery. Tell the person who ordered the report immediately and confirm it in writing rather than waiting for the finished report.
Is a missing RCD always a C2?
No. Best Practice Guide 4 gives a C2 where sockets are likely to supply equipment used outdoors, or where a socket circuit serves a room with a bath or shower. Missing RCD protection for sockets unlikely to be used that way, for domestic lighting circuits or for unprotected cables buried less than 50 mm deep is a C3.
EICRs on your phone

Your EICR, laid out to the model form

Certio lays out EICRs to the BS 7671:2018+A4:2026 model form, records each observation with its code and produces a branded PDF. Photograph the consumer unit and the ways, device types and ratings go into the schedule. Anything it can't read stays blank and anything inferred is flagged for you to confirm. Starter is £5 a month after a 7-day free trial.