Glossary

What is prospective fault current (PFC)? Explained

What is prospective fault current (PFC)? PSCC and PEFC explained, how to measure PFC at the origin, device breaking capacity and the common errors to avoid.

Published 14 September 2026 · Updated 14 September 2026 · Certio Software Ltd

Prospective fault current (PFC) is the highest current that could flow at a point in an installation if a fault of negligible impedance occurred between live conductors (prospective short-circuit current, PSCC) or between a line conductor and earth (prospective earth fault current, PEFC), and it is measured in kA at the origin and recorded on every EIC and EICR. BS 7671 Chapter 43 requires each protective device to have a breaking capacity at least equal to the PFC at its point of installation, which for most domestic MCBs to BS EN 60898 is 6 kA.

Key takeaways
  • PFC is the larger of PSCC (line-to-neutral or line-to-line) and PEFC (line-to-earth) at the origin.
  • It is measured live with the loop function of a multifunction tester at the same time as Ze.
  • Every protective device must have a breaking capacity at or above the PFC where it is installed.
  • UK DNOs can declare up to 16 kA at a single-phase cut-out; measured domestic values are usually 0.5 to 3 kA.
  • PFC is recorded on the EIC and EICR supply characteristics page, not on a Minor Works Certificate.

What is prospective fault current in practice?

When a dead short occurs, the only thing limiting the current is the impedance of the supply and the conductors up to the fault. Close to a large transformer that impedance is tiny and the current can be thousands of amps. The protective device must interrupt it without failing, so the designer needs the worst case, which is at the origin.

In effect PFC ≈ U0 ÷ Z, where U0 is 230 V and Z is the loop impedance to the fault: a Ze of 0.1 Ω gives a PEFC of about 2.3 kA, and a line-to-neutral impedance of 0.05 Ω gives a PSCC of about 4.6 kA. Modern MFTs display PFC directly from the loop measurement.

When is PFC measured?

Certificate PFC recorded? Where
Electrical Installation Certificate Yes Supply characteristics and earthing arrangements
EICR Yes Supply characteristics and earthing arrangements
Minor Works Certificate No Not on the model form

PFC is measured for every new installation, consumer unit replacement and periodic inspection, and at any sub-board, because the breaking capacity of the devices there must suit the value at that point. It matters most in flats and commercial units near a substation, where PFC can exceed the 6 kA rating of standard MCBs; there, 10 kA devices or backup protection from the upstream fuse, as permitted by BS 7671 Regulation 434.5.1, are needed.

How is PFC measured?

The measurement is made with the loop or PFC function of the MFT at the origin, with the installation isolated:

  1. PEFC: test between line and earth, at the same time as Ze with the main earthing conductor disconnected.
  2. PSCC: test between line and neutral. On a single-phase supply this is normally the higher of the two.
  3. Three-phase: test each line to neutral, and line to line where the instrument supports it; otherwise GN3 accepts doubling the highest line-to-neutral value.
  4. Record the highest value as the PFC on the certificate.

The certificate allows the figure to be marked "measured" or "enquiry" (from the DNO's declared maximum). On site, the measured value is expected.

Breaking capacity to compare against

Device Standard Typical rated short-circuit capacity
MCB BS EN 60898 6 kA (some 10 kA)
RCBO BS EN 61009 6 kA (some 10 kA)
Consumer unit assembly BS EN 61439-3 16 kA conditional, relying on the DNO cut-out fuse
BS 88 fuse BS 88-2 / BS 88-3 80 kA

Common mistakes with PFC

  • Recording only PEFC. The form asks for the higher of PEFC and PSCC, and on most supplies PSCC is the larger.
  • Measuring at a socket-outlet. PFC falls with distance from the origin, so a reading at an accessory understates the value the board's devices must handle.
  • Copying the DNO figure and marking it "measured". If it came from an enquiry, tick the enquiry box.
  • Fitting 6 kA devices where PFC exceeds 6 kA without confirming backup protection from the upstream fuse.
  • Forgetting three-phase line-to-line values, roughly double the line-to-neutral figure.

Related terms

How Certio helps

Certio records this on the BS 7671 model forms without the typing: photograph the board to draft the circuit schedule, point the camera at a Megger MFT-X1 to capture readings, or dictate them. Starter is free for 7 days.

Straight answers

Questions

What is the difference between PSCC and PEFC?
PSCC is the prospective short-circuit current, the current that would flow on a fault between line and neutral (or line and line). PEFC is the prospective earth fault current, the current on a fault between line and earth. Both are measured at the origin and the higher of the two is recorded on the certificate as the prospective fault current.
What is a typical PFC in a domestic installation?
Measured values in UK homes are commonly between 0.5 and 3 kA, though flats close to a substation can be higher. Distribution network operators can declare up to 16 kA at the cut-out for a single-phase supply, which is why consumer units to BS EN 61439-3 carry a 16 kA conditional rating.
Why must PFC be less than the breaking capacity of the MCB?
A circuit-breaker has a rated short-circuit capacity, usually 6 kA for a domestic MCB to BS EN 60898, printed in a rectangle on the front. If the fault current exceeds it the device may fail to interrupt the arc and could be destroyed. BS 7671 Chapter 43 requires every device to be able to break the prospective fault current at its point of installation.
How do I measure PFC on a three-phase supply?
Measure between each line and neutral, and between lines where the instrument supports it. Where a line-to-line test is not possible, IET Guidance Note 3 accepts doubling the highest line-to-neutral reading as a conservative estimate of the line-to-line prospective short-circuit current. Record the highest value obtained.
Is PFC recorded on a Minor Works Certificate?
No. The Minor Works Certificate model form in BS 7671 does not include a PFC box, because the work is confined to an existing circuit and the origin is unchanged. PFC is recorded on the Electrical Installation Certificate and the EICR, in the supply characteristics section alongside Ze.
Less typing, same judgement

Down tools at 5. The paperwork's already done.

Certio lays out EICR, EIC, Minor Works and PAT certificates to the BS 7671 model forms and produces branded PDFs. Photograph the board and the schedule drafts itself; point the camera at a Megger MFT-X1 and the reading goes straight in. Starter is free for 7 days, then £5 a month. Pro is £10 a month with unlimited certificates.

Try Starter free for 7 days →

More on EICR software and AI EICR software. Prices exclude VAT.