Glossary

What is Ze? External earth fault loop impedance

What is Ze (external earth fault loop impedance)? Maximum values for TN-S, TN-C-S and TT, how to measure Ze safely at the origin and what a high reading means.

Published 14 September 2026 · Updated 14 September 2026 · Certio Software Ltd

Ze (external earth fault loop impedance) is the impedance, in ohms, of the part of the earth fault loop that lies outside the installation: from the main earthing terminal back through the supply's earth path and the transformer winding to the origin. It is measured once at the origin with the main earthing conductor disconnected, recorded on the supply characteristics page of every EIC and EICR, and compared with the distribution network operator's declared maximum of 0.35 Ω for TN-C-S, 0.8 Ω for TN-S or 21 Ω for TT supplies as quoted in IET Guidance Note 3.

Key takeaways
  • Ze is the supply's contribution to the earth fault loop; Zs for any circuit equals Ze + (R1 + R2).
  • It is a live measurement made at the origin with the installation isolated and the earthing conductor disconnected.
  • Declared maximum values: 0.35 Ω (TN-C-S), 0.8 Ω (TN-S), 21 Ω (TT).
  • A high Ze limits the Zs achievable on every circuit and may need reporting to the DNO.
  • Ze must be measured for each certificate, not copied from a previous one.

What is Ze in practice?

Every earth fault on a TN system flows back to the supply transformer through the distributor's network: the sheath or separate earth core of the service cable on TN-S, or the combined neutral and earth conductor on TN-C-S (PME). On a TT supply the return is through the general mass of earth via the installation's own electrode, so Ze is much higher.

Ze is a property of the supply, not the installation. The electrician cannot reduce it, but must know it because it sets the floor for every Zs in the building: if Ze is 0.3 Ω, no circuit can have a Zs below 0.3 Ω.

When is Ze measured?

Ze is measured and recorded on every Electrical Installation Certificate and every EICR, in the supply characteristics and earthing arrangements section. Minor Works Certificates have no Ze box, but the Zs recorded for the circuit depends on it. It is also measured before connecting equipment sensitive to the earthing arrangement, such as EV charging under BS 7671 Section 722.

Earthing system Typical declared maximum Ze Typical measured range
TN-C-S (PME) 0.35 Ω 0.1 to 0.35 Ω
TN-S 0.8 Ω 0.2 to 0.8 Ω
TT 21 Ω (electrode plus network) A few ohms to 200 Ω, depending on the electrode

Measured values above the declared maximum should be queried with the DNO, since they indicate a supply earth that is not performing as designed.

How is Ze measured?

The procedure in IET Guidance Note 3 is:

  1. Isolate the installation at the main switch and prove dead on the load side.
  2. Disconnect the main earthing conductor from the main earthing terminal (MET), removing the parallel paths through bonding and circuit protective conductors that would give a falsely low reading.
  3. Connect the loop tester between the incoming line conductor and the disconnected earthing conductor and take the reading; the instrument gives the prospective earth fault current at the same time.
  4. Reconnect the earthing conductor, confirm it is secure, and only then restore the supply.

Step 2 is why Ze cannot be taken from a socket-outlet: the reading there is Zs for that circuit. It is also why the installation must be isolated first, since a live installation with its earth removed is a serious hazard.

On a TT system the same method gives Ze including the electrode resistance. BS 7671 requires that resistance to satisfy RA × IΔn ≤ 50 V for the RCD providing fault protection, which is 1667 Ω for a 30 mA device, though GN3 advises a practical limit of 200 Ω for stability.

Common mistakes with Ze

  • Measuring with the earthing conductor connected, which reads Ze in parallel with the bonding and gives a low, meaningless figure.
  • Taking Ze at a socket-outlet. That is Zs.
  • Copying Ze from the previous EICR. A TN-S sheath can corrode through between inspections.
  • Recording the DNO's declared maximum instead of the measured value.
  • Not isolating the installation before disconnecting the earthing conductor.
  • Forgetting the PFC, which the same test gives and which must also be recorded.

Related terms

How Certio helps

Certio records this on the BS 7671 model forms without the typing: photograph the board to draft the circuit schedule, point the camera at a Megger MFT-X1 to capture readings, or dictate them. Starter is free for 7 days.

Straight answers

Questions

What is a typical Ze value?
The distribution network operators' declared maximum values, quoted in IET Guidance Note 3 and the On-Site Guide, are 0.35 Ω for a TN-C-S (PME) supply, 0.8 Ω for TN-S and 21 Ω for TT. Measured values are usually well below those figures; a TN-C-S supply in an urban area often reads 0.1 to 0.2 Ω.
Why is the earthing conductor disconnected to measure Ze?
Because with it connected, the loop tester would also see parallel paths through main protective bonding to gas and water pipes and through other circuits' protective conductors, giving a falsely low reading. Disconnecting the main earthing conductor at the main earthing terminal isolates the supply's own earth path so only Ze is measured.
Is Ze measured with the supply on?
Yes. Ze is a live test. The installation is isolated at the main switch, the main earthing conductor is disconnected and the loop tester is connected between the incoming line and the disconnected earthing conductor. Isolation of the installation is essential because removing the earth from a live installation is dangerous.
What does a high Ze reading mean?
A Ze above the DNO's declared maximum, or much higher than expected, points to a poor supply earth: a corroded sheath on a TN-S cable, a loose or missing PME connection, or a high-resistance electrode on a TT system. It should be reported to the DNO for TN supplies, and it limits the Zs achievable on every circuit.
What is the difference between Ze and Zs?
Ze is the external part of the earth fault loop, measured once at the origin of the installation. Zs is the total loop impedance for an individual circuit, measured at its furthest point, and equals Ze plus the circuit's R1 + R2. Ze appears on the supply characteristics page; Zs appears against each circuit.
Less typing, same judgement

Down tools at 5. The paperwork's already done.

Certio lays out EICR, EIC, Minor Works and PAT certificates to the BS 7671 model forms and produces branded PDFs. Photograph the board and the schedule drafts itself; point the camera at a Megger MFT-X1 and the reading goes straight in. Starter is free for 7 days, then £5 a month. Pro is £10 a month with unlimited certificates.

Try Starter free for 7 days →

More on EICR software and AI EICR software. Prices exclude VAT.

Sources

  1. IET: BS 7671:2018+A4:2026 Requirements for Electrical Installations (18th Edition) and model forms
  2. IET: Guidance Note 3, Inspection and Testing

Checked against these sources on 14 September 2026. This guide is general information for electricians, not legal advice.