Extra-low voltage under BS 7671:2018+A4:2026 is anything not exceeding 50 V AC rms or 120 V ripple-free DC, but the letters in front of "ELV" decide how much protection the circuit needs. SELV and PELV are complete protective measures under Section 414; FELV is not, and Regulation 411.7 sends it back to automatic disconnection like the 230 V circuit feeding it. The practical traps are the source (is the driver actually marked as a safety source?), the wiring (is the separation kept all the way?), volt drop (Regulation 715.525 allows only 0.6 V on 12 V lighting) and the test voltage (250 V DC, 0.5 MΩ minimum, from Table 64).
- ELV is up to 50 V AC rms or 120 V ripple-free DC. SELV and PELV are protective measures in Section 414; FELV is dealt with by Regulation 411.7 and gives no protection by itself.
- A SELV source must be one of those listed in Regulation 414.3: a safety isolating transformer to BS EN 61558-2-6, an equivalent source, a battery or independent source, or an electronic device whose output stays within ELV even under an internal fault. Check the marking.
- SELV is kept apart from earth and from every other circuit. PELV may be earthed. FELV has no protective separation, so its exposed metalwork goes to the primary circuit's protective conductor.
- In normal dry conditions basic protection can be left off SELV up to 25 V AC or 60 V DC (and PELV at those voltages where parts are earthed to the MET). In a bath or shower room it is always needed.
- Insulation resistance on SELV and PELV: 250 V DC, minimum 0.5 MΩ (Table 64). FELV: 500 V DC, minimum 1 MΩ.
- ESF Best Practice Guide 4 codes an electronic SELV source (for example an LED driver) installed in bathroom zone 0, 1 or 2 as C2.
What do SELV, PELV and FELV actually mean?
Part 2 of BS 7671 defines all three, and the differences come down to two questions: is the source a safety source, and is the circuit kept separate from earth?
| Type | Where in BS 7671 | Source | Connected to earth? | Fault protection needed? | Typical example |
|---|---|---|---|---|---|
| SELV | Section 414 | Safety source listed in 414.3 | No, and separated from all other circuits | No | 12 V pond lighting from a marked safety transformer; LED strip on a SELV-marked driver; bell transformer to BS EN 61558-2-8 |
| PELV | Section 414 | As SELV | May be earthed | No | Control circuits in switchgear and panels; some door-entry and BMS supplies |
| FELV | Regulation 411.7 | Any source that fails 414.3, or wiring that fails the separation rules | Exposed metalwork earthed to the primary circuit's cpc | Yes, by the primary circuit's ADS | 12 V lighting on an autotransformer; unmarked "power supply" bricks |
Section 414 treats SELV and PELV as complete measures: both basic and fault protection come from the low voltage plus the separation. FELV gives neither. Regulation 411.7 requires basic protection by insulation suited to the minimum test voltage of the primary circuit, exposed-conductive-parts connected to the primary circuit's protective conductor, and plugs and sockets that cannot be swapped with those of other systems. Disconnection relies entirely on the primary circuit's protective device.
What counts as a SELV source?
Regulation 414.3 lists the sources. The one you will meet most is a safety isolating transformer to BS EN 61558-2-6, built with double or reinforced insulation between windings. The others are a source with an equivalent degree of safety (a motor-generator with equivalent separation, for example), an electrochemical source such as a battery or another independent source, and an electronic device built so that the output cannot exceed ELV even under an internal fault.
That fourth category, 414.3 (iv), is where LED drivers and switch-mode supplies sit. An independent driver marked SELV and made to BS EN 61347-2-13, or a safety isolating supply to BS EN 61558-2-16, meets it. A driver with no SELV marking, or a 12 V lighting transformer that turns out to be an autotransformer, does not. On an EICR the quickest check is the label: no safety marking means you treat the secondary as FELV and inspect it on that basis.
Bell and chime transformers to BS EN 61558-2-8 are safety isolating types. Older units, and modules bundled with some chimes, may give no standard at all; record that as a limitation rather than assuming SELV.
A shaver supply unit to BS EN 61558-2-5 contains a safety isolating transformer, but its output is 230 V or 115 V. That is electrical separation under Section 413, not SELV, so do not record it as an ELV circuit.
How far does the separation have to go?
This is where installations fail. A safety source is not enough; the separation has to survive the wiring. Regulation 414.4 requires protective separation between SELV or PELV circuits and the live parts of any other circuit. In practice that means one of:
- a separate wiring system, kept physically apart from LV cables;
- ELV conductors insulated for the highest voltage present where they share a cable, trunking or enclosure with LV conductors;
- an earthed metallic screen or sheath between the ELV and LV conductors.
Ordinary "LED wire" or speaker cable pulled into the same trunking as 230 V lighting does not meet this unless it is rated for the higher voltage. Inside a fitting or a box, watch where the driver's secondary leads cross mains terminals.
Plugs and socket-outlets for SELV and PELV must not fit sockets or plugs of other voltage systems in the same premises, and SELV plugs and sockets must have no protective conductor contact. A 13 A socket used for a 12 V pond pump fails outright.
For SELV specifically, live parts must not be connected to earth or to another circuit's protective conductor, and exposed-conductive-parts must not be deliberately earthed. A metal SELV luminaire bolted to earthed steelwork stops being SELV. It may still be acceptable as PELV, but PELV is not allowed everywhere SELV is.
When can basic protection be left off?
Regulation 414.4.5 says basic protection is generally not needed in normal dry conditions for SELV not exceeding 25 V AC rms or 60 V ripple-free DC, and for PELV at the same voltages where exposed-conductive-parts and/or live parts are connected by a protective conductor to the main earthing terminal. That is why bare-conductor 12 V track lighting can be legitimate indoors (Section 715 has its own conditions for exposed conductors).
Above those voltages, outdoors, or anywhere wet, basic protection by insulation (Regulation 416.1) or barriers and enclosures to at least IPXXB or IP2X (Regulation 416.2) is required. Section 701 goes further: in a room containing a bath or shower, basic protection is needed for SELV and PELV equipment whatever the voltage.
What are the limits in bathrooms and pools?
| Location | What is allowed | Voltage limit | Source location | Equipment IP |
|---|---|---|---|---|
| Bathroom zone 0 (701) | SELV only | 12 V AC / 30 V DC | Outside zones 0 and 1 | IPX7 |
| Bathroom zone 1 (701) | SELV or PELV (plus listed 230 V fixed equipment with RCD) | 25 V AC / 60 V DC for SELV/PELV | Outside zones 0 and 1 | IPX4 (IPX5 where jets used for cleaning) |
| Pool zone 0 (702) | SELV only | 12 V AC / 30 V DC | Outside zones 0, 1 and 2 | IPX8 |
| Pool zone 1 (702) | SELV only (limited exceptions in 702.55) | 12 V AC / 30 V DC | Outside zones 0, 1 and 2 | IPX4, IPX5 where jets used |
| Pool zone 2 (702) | SELV, 30 mA RCD or electrical separation | ELV limit if SELV used | Per 702.410.3.4.3 | IPX2 indoors, IPX4 outdoors |
NAPIT's January 2022 Section 702 article for Professional Electrician confirms the 12 V AC / 30 V DC limit and the outside-zones-0-1-2 rule for pool zones 0 and 1, and the IP ratings above. For the full zone geometry see our guides to bathroom zones and Section 701 and hot tub and pool wiring under Section 702.
The driver location point catches people. Best Practice Guide 4 Issue 7.2 from Electrical Safety First lists "a source for SELV described in 414.3 (iv) installed in Zones 0, 1 or 2" as C2 in a bath or shower room. A driver lying on top of a ceiling tile directly above the shower tray is a common example.
How much volt drop can 12 V lighting take?
Extra-low voltage means high current. A 60 W load at 12 V draws 5 A; a 300 W transformer can push 25 A into its secondary. Section 715 (extra-low voltage lighting) sets the limit: Regulation 715.525 caps volt drop from the transformer or driver to the furthest luminaire at 5 % of nominal voltage, which is just 0.6 V on a 12 V system. NICEIC's guidance on ELV lighting, published on Voltimum in February 2018, also points to 715.524.201 for minimum conductor sizes and warns that loose secondary terminations in lofts can overheat.
Worked example: 60 W of 12 V LED strip, 8 m from the driver (16 m of conductor out and back), using conductor resistances for class 5 flexible copper at 20 °C from BS EN 60228.
| Conductor size | Resistance (mΩ/m) | Loop resistance (16 m) | Volt drop at 5 A | % of 12 V | Meets 715.525? |
|---|---|---|---|---|---|
| 0.75 mm² | 26.0 | 0.42 Ω | 2.08 V | 17.3 % | No |
| 1.5 mm² | 13.3 | 0.21 Ω | 1.06 V | 8.9 % | No |
| 2.5 mm² | 7.98 | 0.13 Ω | 0.64 V | 5.3 % | No |
| 4.0 mm² | 4.95 | 0.08 Ω | 0.40 V | 3.3 % | Yes |
The same 60 W at 24 V draws 2.5 A, so 1.5 mm² flex drops 0.53 V, which is 2.2 % of 24 V. Doubling the voltage halves the current and quarters the percentage drop, which is why 24 V strip is the better choice for long runs. Real conductors run warmer than 20 °C, so treat these as best-case figures. Our cable sizing and volt drop guide covers the LV side.
Overcurrent protection is not waived by Section 414 either. The secondary conductors need protecting against overload and short circuit under Chapter 43 unless the transformer or driver is short-circuit proof by design. Melted 0.75 mm² flex on old halogen downlight transformers is a regular loft find; see our loft and cellar wiring observations.
How do you test an ELV circuit?
Insulation resistance is the main test. Table 64 of BS 7671 sets the test voltage and minimum value by circuit type:
| Circuit | Test voltage | Minimum insulation resistance |
|---|---|---|
| SELV and PELV | 250 V DC | 0.5 MΩ |
| Up to and including 500 V, including FELV | 500 V DC | 1.0 MΩ |
| Above 500 V | 1,000 V DC | 1.0 MΩ |
Disconnect LED drivers, electronic transformers and any control gear first, both to protect them and because their internal circuitry drags the reading down to a figure that means nothing.
Regulation 643.4.1 then requires the separation of SELV and PELV circuits from other circuits, and of SELV from earth, to be confirmed by insulation resistance measurement, with values to Table 64. With a 230 V primary present the usual approach is to join the ELV conductors together and test them against the LV conductors and earth at 500 V DC, looking for at least 1 MΩ. A low result means the circuit is not separated and cannot be recorded as SELV. The general method is in our insulation resistance testing guide.
Zs, R1+R2 and RCD tests do not apply to a SELV secondary, because there is no protective conductor and no fault path; record N/A. For FELV, test the primary circuit as normal, since its device gives the fault protection, and check continuity of the protective conductor to the FELV equipment's exposed metalwork.
How do you record and code ELV on the certificate?
On the schedule of test results give the ELV circuit its own row with designation, wiring type, conductor size and source, for example "12 V SELV garden lighting via BS EN 61558-2-6 transformer in garage". Enter the insulation resistance at 250 V, and N/A against Zs, R1+R2 and RCD for SELV and PELV. For FELV the row shows the primary circuit's protective device and Zs, because that device disconnects the fault. Column-by-column layout is in how to fill in a schedule of test results.
| Finding | Suggested code | Basis |
|---|---|---|
| Electronic SELV source (LED driver) in bathroom zone 0, 1 or 2 | C2 | ESF BPG4 Issue 7.2, bathrooms |
| Socket-outlet other than SELV or shaver supply within 2.5 m of bathroom zone 1 boundary | C2 | ESF BPG4 Issue 7.2 |
| Shaver supply unit to BS EN 61558-2-5 in zone 2, out of direct spray | No code | Listed as a myth in BPG4 |
| FELV with metal fittings and no protective conductor | Inspector's judgement; normally C2 where touchable metalwork lacks fault protection | 411.7; BS 7671 coding definitions |
| Unmarked transformer or driver, SELV status unknown | Limitation, or FI if in a special location | Treat as FELV until proved |
| ELV conductors sharing trunking with LV, not rated for LV | C3 or C2 depending on condition and access | 414.4 |
| Secondary flex scorched or undersized | C2 where there is a fire risk | Chapter 43, 715.524.201 |
BPG4 does not have specific entries for FELV or mixed wiring, so those rows are judgement calls; write the reason into the observation. Our guide to writing EICR observations that stand up has wording patterns, and EICR codes explained covers the code definitions. Under the A4 forms FI is advisory and does not make the report unsatisfactory by itself; only C1 and C2 do.
How Certio helps
Certio produces the EICR, EIC, Minor Works certificate and PAT records on the BS 7671 model forms and turns them into branded PDFs. Photograph the consumer unit and the circuit schedule drafts itself; point the phone camera at a Megger MFT-X1 and the reading goes straight into the schedule of test results, or dictate it while your hands stay on the probes. Suggested observation wording with the regulation reference is there for you to check and confirm. The judgement stays yours; the typing goes. Starter is £4.99 a month, charged when you sign up.