Section 705 of BS 7671:2018+A4:2026 covers agricultural and horticultural premises, and it is still one of the strictest special locations in the book. Regulation 705.411.1 wants a 30 mA RCD on final circuits feeding sockets up to 32 A and 100 mA or less above 32 A, and the fire rule caps everything else at 300 mA. On a TT shed that 300 mA device means RA must stay at or below 167 Ω (50 V ÷ 0.3 A). Add supplementary bonding for livestock, ammonia, wash-down and rats, and a farm will find every shortcut you take.
- Section 705 covers fixed installations indoors and outdoors where livestock are kept or plants are grown. Rooms for household use are outside its scope.
- RCDs: 30 mA on sockets up to 32 A, 100 mA or less on sockets above 32 A (705.411.1), 300 mA or less on other circuits for fire protection (705.422.7).
- Supplementary bonding is required in livestock locations (705.415.2.1), including any metal grid or reinforcement in the floor.
- Equipment needs IP44 minimum (705.512.2), and switchgear must be out of reach of livestock (705.513.2).
- Livestock heaters must be fixed and at least 0.5 m from animals and combustibles (705.422.6).
- SELECT's A4 summary lists no change to Section 705, so the design rules are as before. The forms and FI coding changed.
- RCD tests are at IΔn since A2. The old 5× test at 30 mA is gone.
Where does Section 705 apply, and where does it stop?
The IEC source standard, IEC 60364-7-705, scopes the section to "fixed electrical installations inside and outdoors of agricultural and horticultural premises". It defines those as rooms, locations or areas where livestock are kept or plants are grown. That means cattle sheds, parlours, pig and poultry units, stables, feed stores, hay and straw lofts, glasshouses and polytunnels with fixed supplies.
It also states that rooms, locations and areas for household applications are not covered. The farmhouse kitchen is not a 705 location. But the standard defines "residences and other locations belonging to agricultural and horticultural premises" as those with a conductive connection to the farm installation. Section 705 has a specific rule for them in its shock-protection clauses (705.411.4), which an IET EngX moderator pointed to in a farm earthing thread. So the house is outside 705, but its earthing can't be ignored when the barn is fed from it.
Two things catch people out:
- Greenhouses with no livestock. NICEIC's 2019 technical article confirms 705 applies to greenhouses of any size, except the rules that only apply where livestock are kept.
- Mixed buildings. A workshop that opens into a stable or a feed store beside the parlour. If animals can get in, or the environment is the same, treat it as 705.
Section 705 adds to the general rules. It doesn't replace them. Chapter 41, Chapter 42, Section 522 and Section 544 all still apply.
What RCD protection does Section 705 require?
| Circuit | Maximum IΔn | Regulation | Why |
|---|---|---|---|
| Final circuits with sockets up to 32 A (not SELV) | 30 mA | 705.411.1 | Additional protection: portable kit, wet floors, metal benching |
| Final circuits with sockets above 32 A | 100 mA | 705.411.1 | Shock protection for 63 A/125 A industrial sockets |
| All other circuits | 300 mA | 705.422.7 | Protection against fire, disconnecting all live conductors |
| Livestock life support (fans, feeding, drinking) | Designed case by case | 705 life-support clauses | A trip must not kill the animals |
The 300 mA rule is about fire, not shock. Dry straw, dust and timber mean a small earth leakage that sits unnoticed for years in a house can smoulder in a barn. NICEIC's answer to a glasshouse design query on Voltimum advises that the 300 mA device should be S-type or time-delayed to avoid nuisance tripping and to discriminate with the 30 mA devices downstream. It should break all live conductors, neutral included.
High-density livestock rearing is the exception. IEC 60364-7-705 defines it as rearing where automatic life-support systems are necessary. A broiler shed can lose birds within hours if the fans trip. Section 705 lets the designer protect those circuits differently and expects an alternative or standby supply where life support depends on electricity. Old 16th Edition guidance even allowed isolators to be left off essential supplies like broiler fans. If you find the fans on a plain 300 mA RCD with nothing to warn anyone, write it up.
How do RA × IΔn and touch voltage work out on a farm?
Most livestock buildings end up TT. Regulation 411.5.3 applies: RA × IΔn ≤ 50 V, where RA is the electrode plus protective conductor resistance.
| RCD | Max RA (50 V rule, current) | Max RA under old 16th Ed 25 V rule | Practical target |
|---|---|---|---|
| 30 mA | 1,667 Ω | 833 Ω | ≤200 Ω (GN3 stability) |
| 100 mA | 500 Ω | 250 Ω | ≤200 Ω |
| 300 mA S-type | 167 Ω | 83 Ω | Well under 167 Ω, allow for dry summers |
| 500 mA | 100 Ω | 50 Ω | Rarely seen now |
The 25 V column is history but it matters. Older farm installations were designed to the 16th Edition, which halved the touch-voltage limit for livestock and expected faster disconnection. You will still find designs and old certificates working to those figures.
Worked check. A cubicle shed on TT with a 300 mA S-type upfront and 30 mA RCBOs on the sockets. Electrode reads 120 Ω in November.
- 300 mA device: 120 × 0.3 = 36 V. Passes 50 V.
- 30 mA RCBOs: 120 × 0.03 = 3.6 V. Passes easily.
- Summer risk: if the reading doubles in a dry July to 240 Ω, the 300 mA device fails (72 V) and you're over GN3's 200 Ω. Drive a second rod or go deeper. Record the season on the schedule.
The 120 Ω figure is illustrative. Measure your own.
Why is supplementary bonding non-negotiable in livestock areas?
A cow stands on four wet hooves on concrete. Its body resistance is low and the current path is long, from a drinking bowl to its back legs. Livestock react to a few volts. A herd that won't drink or milk yields that drop for no reason are classic signs of stray voltage in a parlour.
Regulation 705.415.2.1 requires supplementary equipotential bonding in livestock locations. It connects all exposed-conductive-parts and extraneous-conductive-parts that animals can touch. Where there's a metal grid or reinforcement in the floor, it has to be bonded too.
On a new build that means bonding tails brought out of the mesh before the slab is poured. Then cubicle rails, feed barriers, water troughs, parlour stalls and circuit cpcs all go back to a local bonding bar. It's a job to agree with the groundworker early. On an old slab you can't retrofit the floor grid, which is why so many old parlour EICRs end up with a bonding C2.
For greenhouses, NICEIC notes that fixed metal benching bolted to an earthed frame is an extraneous-conductive-part and needs bonding. Free-standing benching with no good contact to earth doesn't. Main bonding sizes follow Section 544. See the main protective bonding guide.
Should a farm building be PME or TT?
Section 705 bans TN-C downstream of the origin. It doesn't ban a PME supply outright. The worry is a broken PEN. On PME every bonded rail and trough rises with the neutral, and animals feel it well before people do.
NICEIC's greenhouse article sets out three options where PME isn't suitable:
| Option | How it works | Watch for |
|---|---|---|
| TT | Own MET and electrode for the building | RA × IΔn ≤ 50 V (411.5.3); RCDs almost certainly needed |
| TN-C-S (PNB) | Neutral earthed at a single point | Only where the transformer serves just that installation; DNO agreement if they own it |
| Local TN-S | Consumer's isolating transformer, earthed secondary star point | Size and cost |
For TT and local TN-S, there must be no connection between the PME terminal and the building's exposed or extraneous parts. That separation is where farms go wrong. A PV install bonded to the house PME earth. A steel-clad switchfuse for the house mounted on the barn wall. An SWA armour terminated at both ends. The EngX farm earthing thread is a good example of how a TT barn ends up linked back to PME years later. Check what the DNO actually provides. The earthing arrangements guide and the outbuilding supply guide cover the details.
What do the external influences mean for equipment and cables?
Regulation 705.512.2 sets IP44 as the minimum for equipment in normal use. Where conditions are worse, you select for them. On a typical farm the influences that matter are:
- Water. Splashing (AD4) and jets (AD5) in wash-down areas. Parlours and dairies get pressure-washed, so IP65 or IP66 is normal.
- Corrosion. Ammonia from slurry and fertiliser dust (AF). Galvanised steel goes fast. Use stainless or polymer.
- Dust. Grain stores and feed mills (AE). Dust on enclosures is also a fire load.
- Impact. Animals leaning and machinery (AG).
- Vermin. Rats chew PVC.
Regulation 705.513.2 puts switchgear and controlgear out of reach of livestock. Wiring in animal areas must be out of their reach or mechanically protected. SWA, galvanised or polymer conduit, and runs above animal height are the usual answers. Appendix 5 of BS 7671 lists the external-influence codes.
What are the fire rules for heaters and lamps?
Regulation 705.422.6 is short. Heaters used for breeding and rearing livestock must meet their product standard and be fixed. They need at least 0.5 m clearance from the animals and from combustible material, unless the manufacturer asks for more.
That's mostly about infra-red heat lamps for piglets, lambs and chicks. You'll often find them hanging off a nail on their own flex, over straw, swinging within reach of a sow. That fails on fixing and on clearance.
Regulation 705.422.7 is the fire half of the RCD rule: 300 mA or less, disconnecting all live conductors. The general Chapter 42 rules for locations with combustible materials (422.3) and combustible construction (422.4) also apply to timber barns and hay stores. That affects luminaire choice, enclosed fittings and keeping cables clear of stacked bales.
How do you test a Section 705 installation?
The tests are the same as anywhere. The priorities change. IET Guidance Note 3 is the reference.
| Test | Farm-specific point |
|---|---|
| Electrode resistance (TT) | Check against the 300 mA device: 167 Ω max, aim well under GN3's 200 Ω |
| Continuity of supplementary bonding | Low-resistance ohmmeter to each rail, trough, barrier and floor-grid tail. Corroded clamps are normal in parlours |
| Insulation resistance | Damp, dust and ammonia pull readings down. 500 V where possible, 250 V where drives or controls can't be disconnected; Table 64 minimum 1 MΩ |
| Earth fault loop impedance | Long yard runs. Compare with the corrected (80%) max Zs, not the raw table figure |
| RCD operation | Test at IΔn. 30 mA general type trips within 300 ms. A 300 mA S-type is allowed up to 500 ms at IΔn |
| Functional | Check life-support alarms and standby changeover actually work |
Low IR on old sheds is common. Work through the low insulation resistance guide. For RCD test currents and times, see RCD testing explained. For electrode methods, see earth electrode testing on TT systems.
Then the paperwork. Section 705 (705.514.9.3) expects a plan showing equipment locations, concealed cable routes, a single-line diagram and the bonding arrangement. Most farms don't have one. It's not a danger, but it goes in the observations or recommendations.
How do you code Section 705 defects on an EICR?
Use the Electrical Safety First Best Practice Guide 4 approach and your own judgement. Livestock and a combustible environment move a lot of findings up a code compared with a house.
| Finding | Typical code | Reason |
|---|---|---|
| Bare conductors where rodents have stripped a cable | C1 | Live parts accessible |
| Socket circuit up to 32 A with no 30 mA RCD | C2 | Wet, conductive location |
| No RCD at all on non-socket circuits in a barn | C2 | No 300 mA fire protection |
| No supplementary bonding to rails, troughs or floor grid in a livestock area | C2 | Touch voltage to animals |
| TT RA over 167 Ω with only a 300 mA device | C2 | 411.5.3 not met |
| IP20 enclosure in a wash-down area with water ingress | C2 | Water on live parts likely |
| Heat lamp on flex over straw, under 0.5 m | C2 | Fire risk, 705.422.6 |
| Switchgear within reach of livestock, intact | C3 | Damage likely over time |
| PME and TT earths linked by PV, SWA or a shared enclosure | FI | Needs tracing before coding |
| No plan or single-line diagram | Recommendation | Documentation gap |
On the A4 forms FI is advisory. Only C1 and C2 make the report unsatisfactory. If a farm cottage is let in England, a written FI still triggers the landlord's 28-day investigation. For the wider coding logic see EICR observation codes and the ten most common EICR fails.
Did Amendment 4 change anything for farms?
SELECT's "2026 Amendment 4 What's New" summary lists Part 7 changes to Sections 702, 709, 710, 714, 716 and 722. It lists none to Section 705. So the design rules above stand as they were under A2 and A3.
What does reach a farm job is general:
- A4 model forms for EICR and EIC, with FI now advisory.
- Regulations 653.1 and 653.2 on what an EICR must contain and the guidance for recipients.
- Section 714 if you're putting up yard lighting, and Section 722 if there's an EV charger on the farm.
- Site lighting and supplies during construction fall under Section 704. See the temporary supplies guide. Caravans for seasonal workers fall under 708. See the caravan and marina guide.
How Certio helps
Certio produces the EICR, EIC, Minor Works certificate and PAT records on the BS 7671 model forms and turns them into branded PDFs. Photograph the consumer unit and the circuit schedule drafts itself; point the phone camera at a Megger MFT-X1 and the reading goes straight into the schedule of test results, or dictate it while your hands stay on the probes. Suggested observation wording with the regulation reference is there for you to check and confirm. The judgement stays yours; the typing goes. Starter is £4.99 a month, charged when you sign up.