Guide

Smart Meters and Isolators on EICRs: What to Record

How to handle smart meters, missing isolators, meter tails and cut-out problems on an EICR: what you can touch, what to code, what to report to the DNO or supplier.

Published 16 September 2026 · Updated 16 September 2026 · Certio Software Ltd

Most domestic EICRs now start at a smart meter, and a great many of those supplies have no isolator between the meter and the consumer unit. Neither fact is a defect in the installation. BS 7671 requires a main switch at the origin, and Regulation 462.1.201 makes that the linked switch or circuit breaker in the consumer unit, not a separate isolator after the meter. What the missing isolator does affect is how you test safely, what you can measure, and how you write up the supply section. This guide covers that, along with meter tails, cut-out defects, and the smart meter behaviours that confuse readings.

Key takeaways
  • The consumer unit main switch is the required means of isolation at the origin; a separate meter isolator is helpful but not a BS 7671 requirement, so its absence is a limitation, not a code.
  • The cut-out and service cable belong to the DNO; the meter, its seals and the tails up to the isolator belong to the supplier or meter operator. Report faults to the right party and record that you did.
  • A smart meter's remote disconnect contactor is not a means of isolation for the electrician.
  • 25 mm² tails are the norm for a 100 A cut-out fuse; 16 mm² tails carry about 87 A and are usually a C3 unless there is heat damage or a heavy load.
  • Ze measured without disconnecting the earthing conductor must be recorded as measured with parallel paths and the limitation stated.
  • Exposed live parts at a cut-out or meter are a C1 whoever owns them; record the danger, make it safe as far as you can, and report it.

Who owns what at the intake?

The intake is three pieces of equipment with three owners. The service cable, cut-out and cut-out fuse are the distributor's under the Electricity Safety, Quality and Continuity Regulations 2002 (ESQCR); the DNO is responsible for their condition and for the seals. The meter and, where fitted by the supplier, the isolator and the tails between meter and isolator belong to the supplier or its meter operator. Everything from the isolator, or from the meter output terminals where there is no isolator, to the consumer unit is the consumer's installation and is what the EICR covers.

This matters on the report because the EICR is a report on the installation, not on the distributor's equipment. Regulation 644.1.2 in the current edition requires the report to identify the extent of the installation covered and any limitations. Defects in the cut-out or meter still get recorded, because the inspector cannot ignore a danger, but the correct action for a cracked cut-out is a call to the DNO's emergency line and a note on the report, not a quotation to replace it.

A brief map of the intake:

Item Owner Fault reported to Typical EICR treatment
Service cable, cut-out, cut-out fuse, DNO seals Distribution network operator DNO emergency number Record and report; C1 if live parts exposed
Meter, meter seals, tails meter-to-isolator Supplier or meter operator Supplier Record and report; note as outside the installation
Isolator (where supplier-fitted) Supplier Supplier Note presence; not part of the installation
Tails isolator-to-consumer unit, main earthing conductor, main bonding Consumer Consumer or landlord Inspect, test and code as normal

Is a missing isolator a defect?

No. The confusion comes from the practical wish for one, not from the regulations. BS 7671 requires a means of isolation at the origin under Regulation 132.15.201 and 462.1.201, and the consumer unit main switch satisfies that. An isolator between meter and consumer unit is recommended by the ENA and by most DNOs so that the consumer unit can be replaced without withdrawing the cut-out fuse, and many suppliers now fit one free when they exchange a meter, but nothing in BS 7671 makes it mandatory.

On the EICR, a supply with no isolator is written up under limitations rather than observations. The standard wording is along the lines of "No isolator fitted between meter and consumer unit; installation could not be isolated at the origin without withdrawing the cut-out fuse; Ze measured with earthing conductor connected". It is not a C3, because the installation does not depart from BS 7671. Where a consumer unit change is being quoted, the sensible advice to the customer is to have the supplier fit an isolator first, and that note can go in the recommendations rather than as a coded observation.

Withdrawing the cut-out fuse is a separate question. The seal belongs to the DNO and ESQCR Regulation 25 makes interference with distributor equipment an offence. In practice several DNOs allow electricians who are registered with a competent person scheme to remove the fuse for the duration of the work and then report it so a new seal can be fitted; the schemes and the requirements differ between network areas, so check your own DNO's current policy in writing. Where no such scheme applies, book the DNO to remove the fuse or the supplier to fit an isolator, and plan the EICR accordingly.

What does a smart meter change for the inspector?

A SMETS2 smart meter contains a supply contactor that the supplier can open remotely, for example on a prepayment cut-off or a change of tenancy. That contactor is a load switch under the supplier's control. It is not a means of isolation for you: you cannot lock it off, prove it, or rely on it staying open, and it does not meet the requirements of Regulation 462 or Section 537. Everything upstream of the consumer unit main switch is treated as live.

Smart meters also introduce a few behaviours that catch inspectors out. The load switch can open under a supplier command during your test, which looks like a supply failure; if the customer is on a prepayment tariff with a low balance this happens more than you would expect. Some meters take a moment to reconnect after the contactor closes. Some dual-rate meters switch tariff registers through a relay that clicks audibly and can be mistaken for a loose connection. None of this affects the installation, but it is worth knowing before you diagnose a fault that is not there.

The meter tails are where real observations live. For a 100 A cut-out fuse the expected tails are 25 mm² double-insulated single-core cable, rated about 114 A clipped direct from Table 4D1A for 70 °C thermoplastic singles. 16 mm² tails are rated about 87 A in the same configuration, which does not satisfy Regulation 433.1.1 against a 100 A fuse on the face of it. Whether that is a C2 or a C3 depends on the actual conditions: the DNO fuse rating (many older cut-outs carry 60 A or 80 A fuses), the maximum demand of the property, and any signs of overheating. Electrical Safety First Best Practice Guide 4 leaves this to the inspector's judgement. My practice is C3 where the tails are cool, undamaged and the load is modest, and C2 where there is discolouration, a large electric shower or EV charger, or the fuse is confirmed at 100 A with a heavy demand.

Other tails observations that recur: tails run without mechanical protection across a cellar or garage wall (C3, or C2 if the sheath is damaged), tails longer than the supplier's limit of about 3 m without their own fuse protection (C3, with a note that the DNO's requirement is not a BS 7671 regulation), and green/yellow sleeving used on the neutral tail of an older installation (C3 for identification under Regulation 514.3.1). Meter tails with no earth sleeving at all are not an issue because tails have no cpc; the main earthing conductor is a separate 16 mm² conductor from the cut-out or earth block to the main earthing terminal, and that one is inspected under Regulation 542.3.

How do I measure Ze and PFC without an isolator?

Ze is defined as the external earth fault loop impedance measured with the installation's main earthing conductor disconnected, so that parallel paths through bonded pipework do not flatter the reading. Disconnecting that conductor requires the installation to be isolated, and without an isolator or the fuse out you cannot do that safely. Guidance Note 3 accepts a Ze reading taken with the earthing conductor connected provided it is recorded as such and the limitation is stated. The value will be lower than the true Ze, which is unconservative for the disconnection-time check, so if the measured figure is close to the maximum for the supply type (0.35 Ω for TN-C-S, 0.8 Ω for TN-S, 21 Ω for a typical TT) say so and flag it. See What is Ze? External earth fault loop impedance.

Prospective fault current is measured live at the origin between line and neutral and between line and earth, and the higher of the two is recorded. That test is unaffected by the isolator question. If your tester reports 16 kA on a domestic supply, the reading is almost certainly the meter's low impedance rather than a reality; a typical TN-C-S domestic PFC is 1 to 3 kA and the 6 kA breaking capacity of a domestic consumer unit is adequate under the Regulation 536.4.201 conditional short-circuit rating. See What is prospective fault current (PFC)? Explained.

What supply defects are coded on an EICR?

The table shows the common intake findings and how they are usually treated, following Best Practice Guide 4 and NICEIC guidance. As always, the code is the inspector's decision for the installation in front of them.

Finding Owner Usual code Notes
Cracked cut-out with live parts accessible DNO C1 Make safe as far as possible, call DNO emergency line, record on report
Scorching or heat damage at cut-out or meter terminals DNO or supplier C2 (C1 if live parts exposed) Report to owner of the equipment
No isolator between meter and consumer unit n/a Limitation, no code Not a BS 7671 requirement
16 mm² tails on 100 A fuse, no heat damage Consumer C3 C2 if overloaded or damaged
Main earthing conductor undersized or missing Consumer C2 (C1 if no earth at all with exposed metalwork) Regulation 542.3 and Table 54.1
Main bonding to water or gas absent on TN-C-S Consumer C2 Regulation 411.3.1.2
Tails unsheathed or unprotected in a garage Consumer C3, or C2 if damaged Regulation 522
DNO earth terminal present but earthing type unconfirmed DNO FI Request confirmation from DNO before certifying TN-C-S

The last row matters more than it looks. If the earthing conductor is connected to the cut-out but you cannot confirm whether the DNO has provided a TN-C-S or TN-S earth, a Ze reading in the 0.2 to 0.4 Ω range does not tell you which. Record the earthing arrangement as the DNO has declared it, or as unconfirmed with an FI, rather than guessing. For more on the coding framework see EICR observation codes explained: C1, C2, C3 and FI and on the general process How to Do an EICR Step by Step: Inspector's Workflow.

How Certio helps

Certio produces the EICR, EIC, Minor Works certificate and PAT records on the BS 7671 model forms and turns them into branded PDFs. Photograph the consumer unit and the circuit schedule drafts itself; point the phone camera at a Megger MFT-X1 and the reading goes straight into the schedule of test results, or dictate it while your hands stay on the probes. Suggested observation wording with the regulation reference is there for you to check and confirm. The judgement stays yours; the typing goes. Starter is free for 7 days, then £5 a month.

Straight answers

Questions

Is a missing isolator between the meter and consumer unit a C3 on an EICR?
No. BS 7671 requires a main switch at the origin of the installation, which is the consumer unit main switch under Regulation 462.1.201. A separate double-pole isolator after the meter is a convenience that the supplier or DNO may fit. Its absence is not a departure from BS 7671 and is normally noted as a limitation, not coded.
Can an electrician pull the cut-out fuse to isolate a supply?
The cut-out belongs to the distributor under the Electricity Safety, Quality and Continuity Regulations 2002, and breaking its seal without agreement is not permitted. Several DNOs run schemes that allow registered electricians to withdraw the fuse and report it, so check your DNO's policy, otherwise book the DNO or the supplier to fit an isolator.
Are 16 mm² meter tails acceptable on a 100 A cut-out fuse?
16 mm² tails clipped direct are rated about 87 A, so they do not comply with a 100 A fuse on paper. If the DNO confirms the fuse is 80 A or the maximum demand is well under 87 A, many inspectors record it as a C3. Where the tails show heat damage or the load is high, a C2 is justified. 25 mm² is the norm for 100 A.
Does a smart meter's remote disconnect count as a means of isolation?
No. The supply contactor inside a SMETS2 smart meter is a supplier-controlled load switch, not a means of isolation for electrical work. It cannot be secured off by the electrician and does not meet Regulation 462 or Section 537 for isolation. Treat the installation as live upstream of the consumer unit main switch.
Who do I report a damaged cut-out or meter to?
The cut-out and service cable belong to the distribution network operator, so call the DNO's emergency number for cracked cut-outs, exposed live parts or scorching. The meter and its tails to the isolator belong to the supplier or meter operator, so faults on those go to the supplier. Record the report on the EICR and code exposed live parts C1.
Do I need to measure Ze if there is no isolator?
Ze should be measured with the main earthing conductor disconnected, which requires the installation to be isolated. If there is no isolator and you cannot safely withdraw the cut-out fuse, take the reading with the earth connected, record it as Ze measured with parallel paths, and note the limitation on the report.
Less typing, same judgement

Down tools at 5. The paperwork's already done.

Certio lays out EICR, EIC, Minor Works and PAT certificates to the BS 7671 model forms and produces branded PDFs. Photograph the board and the schedule drafts itself; point the camera at a Megger MFT-X1 and the reading goes straight in. Starter is free for 7 days, then £5 a month. Pro is £10 a month with unlimited certificates.