EICR vs EIC: What's the Difference? (and Minor Works)

EICR vs EIC explained: an EICR reports on an existing installation, an EIC certifies new work, Minor Works covers small changes. See which one your job needs.

Published 14 September 2026 · Updated 14 September 2026 · Certio Software Ltd

An EIC (Electrical Installation Certificate) certifies that new electrical work was designed, constructed, inspected and tested to BS 7671 at the time it was done. An EICR (Electrical Installation Condition Report) is a report on the condition of an existing installation, produced after periodic inspection and testing, with defects classified C1, C2, C3 or FI. A Minor Electrical Installation Works Certificate (MEIWC or Minor Works) sits between the two: it certifies a small addition or alteration to a single existing circuit that does not include a new circuit. All three are model forms in BS 7671 Appendix 6, and choosing the wrong one is one of the most common findings at NICEIC and NAPIT assessment visits.

Key takeaways
  • EIC = certificate of new work. EICR = report on existing work. Minor Works = certificate for a small change to one circuit.
  • A new circuit, a consumer unit change or a rewire is always an EIC, never a Minor Works.
  • An EICR cannot certify new work and cannot replace Part P notification.
  • Each certificate has its own signature block: an EIC has designer, constructor and inspector; an EICR has inspector and (where relevant) the person authorising issue; a Minor Works has one.
  • All three must be accompanied by test results: full schedules for EIC and EICR, the specific results for the circuit worked on for Minor Works.

What is an Electrical Installation Certificate (EIC)?

An EIC is the certificate issued for a new installation, an addition or alteration that includes a new circuit, or a replacement of the distribution equipment. It is the document required by BS 7671 Chapter 64 (initial verification) to confirm that the work complies with the Regulations at the time of completion. The EIC comes with a schedule of inspections and a schedule of test results for every circuit installed or affected. The designer of the work also records the recommended interval to the first periodic inspection.

Typical jobs that need an EIC (full detail in the EIC explained):

  • Full or partial rewire.
  • Consumer unit or distribution board replacement.
  • A new circuit of any kind: cooker, shower, EV charger (Section 722), garden supply, extension, loft conversion.
  • A new installation in a new build or an outbuilding.
  • Solar PV or battery storage where a new circuit is created (Section 712, and the new stationary battery chapter in Amendment 4).

In England and Wales, most of this work is also notifiable under Part P of the Building Regulations. A registered competent person (NICEIC, NAPIT and the other scheme operators) notifies the work through their scheme and the client receives a Building Regulations compliance certificate alongside the EIC.

What is an Electrical Installation Condition Report (EICR)?

An EICR is a report on the state of an installation that already exists. It is produced under BS 7671 Chapter 65 (periodic inspection and testing), using the schedule of inspections and schedule of test results, and it lists observations with classification codes:

  • C1 danger present
  • C2 potentially dangerous
  • C3 improvement recommended
  • FI further investigation required

Any C1, C2 or FI gives an overall assessment of Unsatisfactory; C3 alone is Satisfactory (see EICR codes explained). An EICR does not certify anything; it reports. Landlords, buyers and insurers ask for it to know whether the installation is safe to keep using, not whether a particular job was done correctly.

The EICR is the document required every five years for rented homes under the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020, and the equivalent rules in Scotland and Wales. Recommended intervals for other premises are in how often is an EICR required.

What is a Minor Electrical Installation Works Certificate?

A Minor Works certificate is for additions and alterations to an existing circuit that do not include the provision of a new circuit. BS 7671 gives the examples of adding a socket outlet or lighting point to an existing circuit, and relocating a light switch. It is a single-page certificate with the essential test results for the circuit worked on: earthing arrangement, protective device, Zs, insulation resistance, polarity, RCD operation where applicable, and continuity of the cpc.

Typical Minor Works jobs:

  • Adding a spur or socket to an existing ring or radial.
  • Adding or moving a lighting point or switch.
  • Replacing a damaged accessory (socket, switch, ceiling rose).
  • Replacing a like-for-like protective device in an existing board.
  • Repairs carried out as remedial work after an Unsatisfactory EICR, where no new circuit is involved.

Minor Works is not for anything that changes the circuit in a way that requires design: increasing the protective device rating, changing cable size, or extending into a special location such as a bathroom (Section 701). If in doubt, an EIC is always acceptable for small work; a Minor Works for large work is not. See Minor Works certificate: when to use it.

EICR vs EIC vs Minor Works: comparison table

EIC EICR Minor Works (MEIWC)
Purpose Certifies new installation work complies with BS 7671 Reports on the condition of an existing installation Certifies a small addition or alteration to one existing circuit
BS 7671 basis Chapter 64, initial verification Chapter 65, periodic inspection and testing Chapter 64, initial verification of the alteration
When used Rewire, new circuit, consumer unit change, new build Periodic inspection, landlord compliance, sale, insurance, change of use Adding a socket or light to a circuit, replacing an accessory, like-for-like repairs
Covers The new work and anything it affects The whole installation within the agreed extent The circuit that was altered
Outcome Compliant / not issued Satisfactory or Unsatisfactory with coded observations Compliant / not issued
Schedules Schedule of inspections + schedule of test results for all circuits affected Schedule of inspections + schedule of test results for all circuits within extent Test results for the altered circuit on the certificate itself
Signatures Designer, constructor, inspector and tester (can be the same person) Inspector and tester; plus the person authorising issue on behalf of the company One: the person responsible for the work
Part P notifiable (England and Wales)? Usually yes No (it is not work) Usually no, unless in a special location
Next inspection date Recommended by the designer Recommended by the inspector Not applicable
Validity Permanent record of the work Until the recommended next inspection Permanent record of the work

Which certificate applies in common situations?

Situation Certificate
Landlord needs five-yearly electrical safety check EICR
Consumer unit replaced EIC (plus Part P notification)
New cooker circuit EIC
New socket added to kitchen ring Minor Works
Bathroom light replaced like-for-like Minor Works
New shower circuit in bathroom EIC (special location, new circuit)
EICR showed missing main bonding; bonding installed Minor Works (or EIC if the electrician prefers)
EICR showed C2 on socket circuit; RCD added to existing board Minor Works for the alteration, though many electricians issue an EIC because the board has been altered
EV charger installed EIC (Section 722, new circuit)
House purchase, buyer wants to know condition EICR
Full rewire EIC
Insurance requires proof of periodic testing EICR
Extension with several new circuits EIC

The grey areas are remedial jobs after an EICR. If you created a new circuit or replaced the board, it is an EIC; otherwise Minor Works is acceptable. A fresh EICR after extensive remedial work is also fine and often what a letting agent prefers. See Unsatisfactory EICR: what happens next for the detail.

Who can sign each certificate?

BS 7671 does not define who may sign; the requirement is that the person is competent for what they sign for. In practice:

  • EIC: three roles, designer, constructor, and inspector and tester. On a small domestic job one electrician signs all three. On a larger job the designer may be a consultant and the constructor a contractor. Each signatory is responsible only for their part.
  • EICR: signed by the inspector and tester who did the work. Where a company issues the report, there is also a signature by the person authorising issue on behalf of the company, who is usually the qualified supervisor. The inspector should hold a recognised inspection and testing qualification (City & Guilds 2391 or equivalent) and current 18th Edition.
  • Minor Works: one signature by the person responsible for the design, construction, inspection and testing of the minor work.

For notifiable work in England and Wales, the person or business must be registered with a Part P competent person scheme (NICEIC, NAPIT, and others) to self-certify; otherwise the work must be notified to the local authority building control before it starts. Scheme registration is what most clients and letting agents mean when they ask if an electrician is "qualified to sign".

What changed with Amendment 4?

BS 7671:2018+A4:2026, published 15 April 2026, updates the model forms in Appendix 6 to reflect the new content on stationary secondary batteries and functional earthing, and the revised Section 710 for medical locations. The three certificate types and their purposes are unchanged. Certificates issued to the A2 forms remain valid; from 15 October 2026, when A2 is withdrawn, new certificates should be to the A4 forms. Use the current edition of the form your scheme provides.

How Certio helps

Certio produces the EICR, EIC, Minor Works certificate and PAT records on the BS 7671 model forms and turns them into branded PDFs. Photograph the consumer unit and the circuit schedule drafts itself; point the phone camera at a Megger MFT-X1 and the reading goes straight into the schedule of test results, or dictate it while your hands stay on the probes. Suggested observation wording with the regulation reference is there for you to check and confirm. The judgement stays yours; the typing goes. Starter is free for 7 days, then £5 a month.

Straight answers

Questions

What is the difference between an EICR and an EIC?
An EIC (Electrical Installation Certificate) certifies that new electrical work, such as a rewire, a new circuit or a consumer unit change, was designed, built and tested to BS 7671 at the time it was done. An EICR (Electrical Installation Condition Report) reports on the condition of an existing installation at a later date and classifies any defects. One is a certificate of new work; the other is a report on old work.
Do I need an EICR if I have an EIC?
Not immediately. An EIC covers the installation from the date of the work until the first periodic inspection, at the interval the designer recommended on the certificate. For a rental in England, the 2020 Regulations accept an EIC for a new installation in place of an EICR for five years. After that, or if the installation has been altered or damaged, an EICR is needed.
When can a Minor Works certificate be used instead of an EIC?
A Minor Electrical Installation Works Certificate is for additions or alterations to an existing circuit that do not include a new circuit: adding a socket to a ring, replacing a light fitting, moving a switch, replacing a damaged accessory. A new circuit, a consumer unit replacement or a rewire always needs an EIC. Replacing a protective device like-for-like can be a Minor Works; changing the board cannot.
Is a consumer unit change an EIC or a Minor Works?
An EIC. Replacing a consumer unit is treated as a new installation of the distribution equipment and requires design, construction and full inspection and testing of every circuit connected to it. It is also notifiable under Part P of the Building Regulations in England and Wales, so it should be done by a registered competent person or notified to building control.
Who can sign an EIC?
An EIC has three signatures: designer, constructor and inspector/tester, each signed by a competent person, and they may all be the same person on a small job. Each signatory takes responsibility for their part. There is no legal register of who can sign, but the signatory must be competent for the work and in England and Wales notifiable work must go through a Part P competent person scheme or building control.
Can an EICR be used instead of an EIC for new work?
No. An EICR only reports on condition; it does not certify that work was designed and constructed to BS 7671 and it does not satisfy Part P notification. If new work has been done without an EIC, a later EICR can confirm the installation is in a satisfactory condition, but it does not retrospectively certify the work, and building control may still require regularisation.
Less typing, same judgement

Down tools at 5. The paperwork's already done.

Certio lays out EICR, EIC, Minor Works and PAT certificates to the BS 7671 model forms and produces branded PDFs. Photograph the board and the schedule drafts itself; point the camera at a Megger MFT-X1 and the reading goes straight in. Starter is free for 7 days, then £5 a month. Pro is £10 a month with unlimited certificates.